Launch fiber specifications - OptiFiber Pro
Fluke Networks offers launch cords with reference grade connectors in accordance with standards such as ANSI/TIA-526-14-C and ISO/IEC 14763-3. The requirements of these standards for loss at the connector are 0,10 dB for multimode and 0,20 dB for singlemode.
Our launch cords are made to the following specifications:
Multimode 50/125 µm
- Cable: Prysmian, MaxCap-OM3
- Jacket/Trim color: Aqua
- Insertion Loss (reference grade)1 0,1 dB maximum
- Return Loss: máximo de 40 dB
- Radius of Curvature per GR-326: 7 mm to 25 mm
- Apex Offset per GR-326: 0 to 50 µm
- Fiber Height (spherical fit) per GR-326: -100 nm to + 100 nm
- Angular Offset per GR-326: -0,3 degrees to +0,3 degrees
- Fiber Roughness (Rq) per GR-326: 0 to 50 nm
- Ferrule Roughness (Rq) per GR-326: 0 to 50 nm
- Length: 105 m ± 3 m
Multimode 62,5/125 µm
- Cable: OFS, Laser Optimized 62,5 XL ±1,0 μm core diameter
- Jacket/Trim color: Orange
- Insertion Loss (reference grade)1 0,1 dB maximum
- Return Loss: máximo de 40 dB
- Radius of Curvature per GR-326: 7 mm to 25 mm
- Apex Offset per GR-326: 0 to 50 µm
- Fiber Height (spherical fit) per GR-326: -100 nm to + 100 nm
- Angular Offset per GR-326: -0,3 degrees to +0,3 degrees
- Fiber Roughness (Rq) per GR-326: 0 to 50 nm
- Ferrule Roughness (Rq) per GR-326: 0 to 50 nm
- Length: 105 m ± 3 m
Singlemode 9/125 µm (UPC)
- Cable: Corning, SMF 28e+
- Jacket/Trim color: Yellow
- Insertion Loss (reference grade)2 0,2 dB maximum
- Return Loss: máximo de 50 dB
- Radius of Curvature per GR-326: 7 mm to 25 mm
- Apex Offset per GR-326: 0 to 50 µm
- Fiber Height (spherical fit) per GR-326: -100 nm to + 100 nm
- Angular Offset per GR-326: -0,3 degrees to +0,3 degrees
- Fiber Roughness (Rq) per GR-326: 0 to 50 nm
- Ferrule Roughness (Rq) per GR-326: 0 to 50 nm
- Length: 160 m ± 3 m
Singlemode 9/125 µm (APC)
- Cable: Corning, SMF 28e+ (Non bend insensitive)
- Jacket/Trim color: Yellow/Green
- Connector color: Green
- Step or conical endface: Step
- Insertion Loss (reference grade) 0,15 dB maximum3
- Return Loss: máximo de 65 dB
- Radius of Curvature per GR-326: 5 mm to 12 mm
- Apex Offset per GR-326: 0 to 50 µm
- Fiber Height (spherical fit) per GR-326: -100 nm to + 100 nm
- Angular Offset per GR-326: 7,8 degrees to 8,2 degrees
- Fiber Roughness (Rq) per GR-326: 0 to 50 nm
- Ferrule Roughness (Rq) per GR-326: 0 to 50 nm
- Length: 160 m ± 3 m
1Maximum insertion loss for 2,5 mm ferrules is based on interoperability and 2 standard deviations. For maximum insertion loss, 95% should meet the specification. During testing of the insertion loss using a master test cord (MTC), the maximum allowed test is to be less than 0,07 dB to achieve interoperability
2Maximum insertion loss for 2,5 mm ferrules is based on interoperability and 2 standard deviations. For maximum insertion loss, 95% should meet the specification. During testing of the insertion loss using a master test cord, the maximum allowed test should be less than 0,17 dB to achieve interoperability
3Except for E2000 which is 0,40 dB maximum.
- Temperatura -20°C a 60°C
- Relative Humidity (%RH operating without condensation): 95% (10°C to 35°C); 75% (35°C to 40°C) uncontrolled < 10°C
- Vibração: Aleatório, 2g, 5-500 Hz