Diagnosing wiremap faults - MicroScanner2 | Fluke Networks

Base de conhecimento

KB Home   >  Teste de cobre   >  MicroScanner2

Diagnosing wiremap faults - MicroScanner2

Listed are the typical causes of wiremap failures.

Aberto

  • Wires connected to wrong pins at connector or
  • Punchdown blocks
  • Faulty connections
  • Damaged connector
  • Damaged cable
  • Wrong pairs selected in setup
  • Wrong application for cable

Split Pair

  • Wires connected to wrong pins at connector or punchdown block

Pares invertidos

  • Wires connected to wrong pins at connector or punchdown block

Crossed Pairs

  • Wires connected to wrong pins at connector or punchdown block
  • Mix of 568A and 568B wiring standards (12 and 36 crossed)
  • Crossover cables used where not needed (12 and 36 crossed)

Short

  • Damaged connector
  • Damaged cable
  • Conductive material stuck between pins at connector
  • Improper connector termination
  • Wrong application for cable

Autor: Fluke Networks

Data de criação: 25-2-2014

Última alteração: 25-2-2014

 
 
 
 
Powered By OneLink